| pof_lv_switchgear_and_other {CNAIM} | R Documentation | 
Current Probability of Failure for LV switchgear and others
Description
This function calculates the current annual probability of failure for LV switchgear and others The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function. For more information about the probability of failure function see section 6 on page 34 in CNAIM (2021).
Usage
pof_lv_switchgear_and_other(
  lv_asset_category = "LV Circuit Breaker",
  placement = "Default",
  altitude_m = "Default",
  distance_from_coast_km = "Default",
  corrosion_category_index = "Default",
  age,
  measured_condition_inputs,
  observed_condition_inputs,
  reliability_factor = "Default"
)
Arguments
| lv_asset_category | String The type of LV asset category | 
| placement | String. Specify if the asset is located outdoor or indoor. | 
| altitude_m | Numeric. Specify the altitude location for
the asset measured in meters from sea level. | 
| distance_from_coast_km | Numeric. Specify the distance from the
coast measured in kilometers.  | 
| corrosion_category_index | Integer. Specify the corrosion index category, 1-5. | 
| age | Numeric. The current age in years of the conductor. | 
| measured_condition_inputs | Named list observed_conditions_input | 
| observed_condition_inputs | Named list observed_conditions_input
 | 
| reliability_factor | Numeric.  | 
Value
DataFrame Current probability of failure per annum per kilometer along with current health score.
Source
DNO Common Network Asset Indices Methodology (CNAIM), Health & Criticality - Version 2.1, 2021: https://www.ofgem.gov.uk/sites/default/files/docs/2021/04/dno_common_network_asset_indices_methodology_v2.1_final_01-04-2021.pdf
Examples
# Current annual probability of failure for LV Switchgear and other
pof_lv_switchgear_and_other(
lv_asset_category = "LV Circuit Breaker",
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 10,
observed_condition_inputs =
list("external_condition" =
list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("operational_adequacy" =
list("Condition Criteria: Operational Adequacy" = "Default")),
reliability_factor = "Default")