pof_future_board_04kv {CNAIM} | R Documentation |
Future Probability of Failure for 0.4kV Board
Description
This function calculates the future annual probability of failure per kilometer 0.4kV board. The function is a cubic curve that is based on the first three terms of the Taylor series for an exponential function.
Usage
pof_future_board_04kv(
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age,
measured_condition_inputs,
observed_condition_inputs,
reliability_factor = "Default",
k_value = 0.0069,
c_value = 1.087,
normal_expected_life = 60,
simulation_end_year = 100
)
Arguments
placement |
String. Specify if the asset is located outdoor or indoor. |
altitude_m |
Numeric. Specify the altitude location for
the asset measured in meters from sea level. |
distance_from_coast_km |
Numeric. Specify the distance from the
coast measured in kilometers. |
corrosion_category_index |
Integer. Specify the corrosion index category, 1-5. |
age |
Numeric. The current age in years of the conductor. |
measured_condition_inputs |
Named list observed_conditions_input |
observed_condition_inputs |
Named list observed_conditions_input
|
reliability_factor |
Numeric. |
k_value |
Numeric. |
c_value |
Numeric. |
normal_expected_life |
Numeric. |
simulation_end_year |
Numeric. The last year of simulating probability of failure. Default is 100. |
Value
DataFrame. Future probability of failure along with future health score
Examples
# Future annual probability of failure for 0.4kV board
pof_future_board_04kv(
placement = "Default",
altitude_m = "Default",
distance_from_coast_km = "Default",
corrosion_category_index = "Default",
age = 10,
observed_condition_inputs =
list("external_cond" =
list("Condition Criteria: Observed Condition" = "Default"),
"compound_leaks" = list("Condition Criteria: Observed Condition" = "Default"),
"internal_cond" = list("Condition Criteria: Observed Condition" = "Default"),
"insulation" = list("Condition Criteria: Observed Condition" = "Default"),
"signs_heating" = list("Condition Criteria: Observed Condition" = "Default"),
"phase_barriers" = list("Condition Criteria: Observed Condition" = "Default")),
measured_condition_inputs =
list("opsal_adequacy" =
list("Condition Criteria: Operational Adequacy" = "Default")),
reliability_factor = "Default",
k_value = 0.0069,
c_value = 1.087,
normal_expected_life = 60,
simulation_end_year = 100)